Secure Interlock - man trap Door Control
The #4900 series door interlock controller
can provide power and control for up to
128 doors.
The PLC logic allows only one
door, in any defined area, to be unsecured
at a time. Simultaneous requests for
access or requests for access while another
door is unsecured are denied to maintain
the highest level of control.
Environmental or Security Control
Suitable for air locks or security mantraps,
this door interlock system will effectively
control normally unlocked doors, normally
locked doors or any combination of both.
The controller may also be customized to
control automatic door openers and provide
timing and logic sequences for biological
wash-down and air purging controls.
Fail-safe or Fail-secure Locks
Lock control relays with DPDT outputs
allow use of 12 or 24 volt DC fail-safe
maglocks and fail-secure electric strikes.
Both types can be used simultaneously on
the same doors.
Access Control Compatible
Any access control system can be used
with the 4900 series controllers. The
request for access input recognizes any
normally open dry contact.
Optional 12/24 VDC Lock Power
While the PLC controller requires regulated
12 or 24 VDC input, the intergral 4204
power supply also provides ample 12 or 24
VDC output to operate maglocks and/or
strikes for each of the doors. The heavyduty
power supply is ready for hook-up to
the fire alarm system. An alarm output is
also provided for monitoring the control
system.
Traffic Control Indicators
The DPDT relay outputs can also be used
to control lighted door status indicators;
which provide users with visual feedback
as to when a door may be accessed. For
user convenience, a green light is typically
used to signify that a door is ready for
access and a red light to indicate that a
door is un-accessible. Dortronics
#7201xL2-H hi-intensity LEDs are ideal for
use with this system.
Description:
#4900-PLC - Programmable controller
capable of interfacing with up
to sixteen I/O modules for a
total capacity of 128-Inputs
and 128-Outputs
#4900-I/O Module - Eight digital Optically
isolated inputs accept
dry contact signals from door
status switches and requestfor-
access devices such as
push buttons or card access
systems. Four DPDT relay
outputs provide control for
maglocks, strikes, traffic lights
or other low voltage devices.
The #4900-I/O module has
Additional capability providing
Digital outputs which may be
utilized for up to four more
relays controlled by the PLC
Operation:
Only one door may be unlocked or
open at one time. Unlocking or opening
one door automatically secures all
other doors within the designated
area. A request for access at any
normally locked door will inhibit the
REX inputs for all other doors in the
area.
Lock relay contacts will allow low voltage
red and green LEDs to be utilized
for user feedback. Typically a green
light indicates that access is permitted,
while a red light signals that
another door is open and access is
denied at this door.
Other customized operations may be
factory programmed to allow timed
sequences, etc. Program changes
can be emailed for field uploading onsite.
Call for additional information
and pricing.
Specifications:
Enclosure- 12” x 16” x 4” deep
NEMA enclosure will accommodate
PLC controller & one
I/O module with power supply.
Additional modules require
larger enclosures.
PLC Module - 6-1/8” x 3-3/8” overall
I/O Module - 10’ x 3” overall
Electrical - AC Input - Fused 110 VAC
DC Output - 4 amp field
selectable 12 or 24 VDC
Inputs - Door Status (Dry contact
closed when is door secure)
Request for Access (Dry contact
normally open)
Relay Outputs - DPDT Contacts rated
3 Amps @ 28 VDC for each
door (Magnetic lock or strike
& LED traffic indicators for
each door. One common on
each relay is fused.
We have found this manufacturer to be extremely user friendly !
Please note: this item is a highly customizable product. Because of the nature of this product we encourage you to all us to go over your need before you place your order. This way we will have an idea of what your installation will be and try to set it up accordingly. The great benefit of doing this is that when your system arrives it will work for your installation perfectly.